Sign In | Join Free | My lightneasy.org |
|
Brand Name : Eltek
Model Number : CDEJ6042.xxxx
Certification : CE.UL
Place of Origin : CN
MOQ : 1
Payment Terms : L/C,T/T
Supply Ability : 400 sets /month
Delivery Time : 8-10 weeks
Packaging Details : wooden cartons
Brand : Eltek
Produft name : Indoor Rectiverter scable cabinet
Protection level : SPD , LLVD. BLVD
Input current : 1920 ADC
Max input AC : 320 - 475 VAC
Max input DC : 40 - 58 VDC
Mains configuration : 230/400VAC 3 phase (Y)
Max AC output : 346 - 415 VAC
Max output power : 90 kva/ 72kw
DC output power : 72 kW
DC output current : 1500 ADC
DC max voltage : 58 VDC
IP grade : IP20/IP21
Eltek Rectiverter-Indoor system Scalable 120 kW system with optional A+B, AC input (CDEJ6042.xxxx)
The scalable Rectiverter indoor system provides backup power for 400 VAC 3-phase or 230 VAC 1-phase loads, and 48 VDC power for DC loads and battery charging.
The system has a maximum load capacity of 108 kW, which is dynamically variable to provide AC outputs up to 90 kVA / 72kW and also feed DC loads up to 72 kW with built in AC & DC distribution.
When used in combination with the optional B-input (dual AC input) which eliminates the need for a traditional ATS (Automatic Transfer Switch), the Rectiverter indoor system represents the ultimate in flexibility and scalability.
400 VAC 3 phase (Y) input
400 VAC 3 phase (Y) output
48 VDC input/output
Max 90 kVA / 72 kW AC output
Max 72 kW DC output
AC Distribution
DC distribution option
A+B option (dual AC input)
LVBD option
Up to 4 battery strings
Built in transfer technology
150% overload capability, 15S
600% quick trip current 20 ms
Hot pluggable
Smartpack2 controller
Operates in paralell with Flatpack2 rectifiers
Global compliance
Patented HE technology
SINGLE LINE DIAGRAM 120 KW + 108 KW B-INPUT
Parameters :
Models / ordering information | 120 kW + 108 kW B-input | ||
Product family | CDEJ6042.xxxx | ||
AC OUTPUT DATA | |||
Voltage (default) / (adjustable range)1) | 400 VAC 3 phase (Y) / 346-415 VAC | ||
Frequency (default inverter mode) | 50 Hz (adaptive) | ||
Frequency (set-able inverter mode) | 50Hz, 60Hz or last synced 50/60Hz (adaptive) | ||
Power maximum (continuous / overload (<15s) ) | 72 kW (90 kVA) / 120kVA | ||
Current maximum/phase (continuous / overload (<15s) ) | 130 ARMS / 174 ARMS | ||
Current (maximum) Quick trip/phase (20ms) | 640 A (6 x nominal) | ||
Hold up (Voltage dips) (before switching to battery) | > 5 ms @ 72 kW load | ||
THD | < 1.5 % at resistive load | ||
Output features | Module: Fuse in L and N , Hot pluggable 1 pole or 3 pole AC distribution (connection directly on MCB) Max breaker capacity according to recommended max breaker for rectiverter module | ||
DC OUTPUT DATA | |||
Voltage (default) / (adjustable range) | 53.5 VDC / 43 - 58 VDC | ||
Power (maximum @nominal input) | 72 kW 2) | ||
Current (maximum @VOUT ≤ 48 VDC) | 1500 A 2) | ||
Hold up time, maximum output power | >10ms; VOUT > 41 VDC | ||
Output features | Short circuit proof, Over voltage Shutdown | ||
INPUT DATA | |||
AC Mains Input Voltage(3 phase Y) | 320-475 VAC, | ||
AC Current/phase(at nominal output voltage) (depending on module type) | 140-240 ARMS 4) | ||
Frequency (default: sync range) | 47-53 & 57-63 Hz | ||
Frequency (set-able: sync range) | 47-53 Hz, 57-63 Hz or both (adaptive) | ||
Power Factor / THD | > 0.99 at 50% load or more / < 3.5% | ||
DC Voltage nominal / extended range (no overload)3) | 45 - 58 VDC / 40 - 45 VDC | ||
DC Current (maximum) | 1920 A / 2700 A during overload (15s) | ||
Input features | Module : Fuse in L and N, Hot pluggable, Varistor, Hot pluggable AC input individual screw terminals 150 mm2 for L1-L3, N & PE | ||
BATTERY BREAKER | |||
1-pole battery breaker | 2*TPS 2 holder (800-1600 A) | 4*TPS 00 holder (250-600 A) | |
OPTIONS | |||
B-input maximum power (with FP2 HE, 2 kW rectifiers) | 72 kW | ||
B-input maximum power (with FP2 HE, 3 kW rectifiers) | 108 kW | ||
DC distribution (connection directly on breaker) | 1-125 A, 1 pole breaker (max 30 pc 18 mm, max 20 pc 27 mm) | ||
LVBD (1-pole) | 1800 A | ||
OTHER SPECIFICATION | |||
Efficiency | >96% (mains mode (AC/AC and AC/DC)), >94% (inverter mode (DC/AC)) | ||
Protection Class | IP 20 | ||
Operating temperature | -40 to +55°C (-40 to +131°F), humidity 5 - 95% RH non-condensing | ||
Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing | ||
Dimensions[WxDxH] / Weight | 1200 x 600x 2000mm (23,7 x 23,7 x 78,8”) / 300 kg (1100 lbs) | ||
DESIGN STANDARDS | |||
Electrical safety | EN 60950-1, EN 62040-1 UPS safety | ||
EMC | ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15 EN 61000-6-1 /-2/-3/-4, EN62040-2 | ||
Environment | ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) Normal operating conditions to be as per IEC/EN 62040-3:2011 clause 4.1 RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant | ||
1) Output voltage ranges configured in factory and have individual keying in top chassis 3) 40 - 45 VDC: reduced performance - no power boost and increased voltage THD on AC output. | 2) AC load has priority. Maximum available DC output power and current is dependent on instant AC load and AC input voltage; i.e maximum 48kW/1000 A at full AC power and nominal input for 230VAC. 4) If DC voltage is pulled below 43V the input current may increase above this level |
* The indoor Rectiverter Cabinet with AC &DC feed in one cabinet
Related Products :
Solutions
For telecom enterprises at home and abroad, we provide a comprehensive range of services. From on - site inspections to gain a practical understanding of the situation, to the formulation of professional plans based on customer demands, and then to the resolution of technical issues and the regular maintenance of equipment, we cover it all. With a highly qualified team and a network of reliable partners worldwide, we guarantee the efficiency and reliability of our services.
FAQ :
1.How do you supervise product quality?
2.Is there a minimum quantity for placing an order?
3.Can you introduce your company briefly?
4.What are the competitive edges of your company?
5.Can I ask for samples and get a price quotation?
![]() |
Rectiverter Eltek Telecom Power System Scalable 120kW 230/400VAC 3 Phase Big System Images |